The EVO™ Pressure Transducer is typically installed in the leak detector port of the submersible pump manifold. During the AUTO-LEARN® setup process, EVO™ learns the pressure decay curve characteristics of a calibrated leak.
During non-pumping periods, the EVO™ will conduct line leak testing by comparing the line pressure changes to those learned during the AUTO-LEARN® process. A deviation in pressure, such as a drop beyond predefined thresholds, will be declared as a leak and shut down the associated submersible pump.
With declaration of a leak, the system will notify the operator via the EVO™ display with additional email or SMS notification through the FFS PRO® Connect Web Browser Interface.