NEXPHASE™ Smart EV Switchgear

NEXPHASE™ Smart EV Switchgear

The NexPhase™ Smart EV Switchgear is a turnkey EV charging infrastructure solution. NexPhase™ integrates all necessary components required between the utility service and Level 3 DC fast chargers into an all-in-one panel solution.

THE NEXPHASE™ ADVANTAGE

NexPhase™ features cutting-edge grid intelligence for utility power and EV charger remote monitoring, troubleshooting, and control. As the vital link between the utility power and chargers, NexPhase™ provides uptime features that chargers alone cannot offer. 

Integrated power distribution / utility termination solution


Remotely monitored & controlled circuit breakers


Embedded power quality monitoring with advanced analytics


Remote EV charger hard reboot capabilities

Advanced charger outage troubleshooting


Facilitates greater charger uptime


Universal charger compatibility


EUSERC compliant, UL Listed

NxPh1600-Double.png

 

BRANCH BREAKERS (MAXIMUM)

Up to 4 x 400 A or 2 x 600 A

CHARGER CONFIGURATIONS

Up to 4 x 200 kW or 2 x 360 kW

TURNKEY EV CHARGING ELECTRICAL INFRASTRUCTURE

NexPhase™ combines all of the electrical panels, equipment, and wiring that are tasked with receiving, distributing, and protecting a DC fast charging site’s power.

Nexphase - Icon - Planning.psd

SIMPLIFY PLANNING

As a turnkey solution, NexPhase™ combines all traditional post-and-frame switchgear equipment into a single enclosure, eliminating the lengthy design and permitting process. NexPhase™ provides an integrated, single-cabinet, ready-to-install switchgear solution.

Nexphase - Icon - Purpose-Built.psd

PURPOSE-BUILT FOR EV

NexPhase™ is designed specifically for electric vehicle DC fast charger applications. It combines the utility termination cabinet, utility current transformer cabinet (CT), main service breaker, and 480 V 3-phase branch breakers into a single, UL 891 listed / NEMA rated enclosure for outdoor environments.

Nexphase - Icon - Commissioning.png

RAPID COMMISSIONING

NexPhase™ requires only the on-site connections for incoming utility power, utility meter connection, and outgoing charger connections, drastically reducing on-site installation time and costs.

Nexphase - Icon - Chargers.psd

CHARGER FLEXIBILITY

Integrated adjustable circuit breakers allow NexPhase™ to accommodate a wide range of DC fast charger kW ratings and site configurations, regardless of the charger manufacturer.

Nexphase - Icon - Utility.psd

UTILITY-READY

With an integrated meter socket and test switch plate, current transformer mounting plates, and utility service connections, NexPhase™ is ready to accommodate your local utility connections.

Nexphase - Icon - EUSERC.psd

EUSERC COMPLIANT

Franklin Electric has worked with EUSERC since 2022 to ensure NexPhase™ meets their stringent design guidelines and is suitable for utility applications. With involvement from 80 utilities across 14 states, the EUSERC committee promotes uniform electric service requirements among its member utilities and establishes manufacturing and installation requirements for metering and service equipment. 

EV CHARGING SITE SIMULATOR

Learn how to boost uptimes and reduce maintenance costs with NexPhase™

INTELLIGENT MONITORING & CONTROL

At the core of NexPhase™ lies a commitment to charger reliability. With innovative features designed to streamline operations, reduce maintenance costs, and mitigate downtime, NexPhase™ sets a new standard for charger reliability and performance.

Nexphase - Icon - Connected.psd

CONNECTED INFRASTRUCTURE

Unlike any switchgear of its kind, NexPhase™ features cutting-edge grid intelligence for switchgear and EV charger remote monitoring, troubleshooting, and control. As the vital link between the utility power and chargers, NexPhase™ provides uptime features and power analytics that chargers alone cannot offer.

Nexphase - Icon - Power Cycle.psd

REMOTE POWER CYCLING

Charger outages are routinely caused by a charger software or communication failure. Most frequently a hard power cycle of the charger is all that is needed to get the charger up again. The charge point operator simply cannot perform a hard reboot of a charger without sending a technician to the site. With NexPhase™, charge point operators can remotely cycle the circuit breakers avoiding extended downtime and costly maintenance calls.

Nexphase - Icon - Uptime.psd

INCREASE CHARGER UPTIME

With early detection of charger deficiencies and power availability provided by NexPhase™, operators are provided with the tools to identify outages, improve uptime, and enhance the reliability of their EV charging sites.

Nexphase - Icon - Power Quality.psd

POWER QUALITY MONITORING

With near real-time monitoring of critical incoming utility power parameters such as Current, Voltage, Power Factor, Apparent Power, Active Power, and Reactive Power, an embedded power quality monitor empowers charge point operators with actionable data insights to optimize charger performance, apply predictive maintenance, and mitigate downtime.

Nexphase - Icon - Safety.psd

SAFETY FEATURES

NexPhase™ offers integrated surge protection, ensuring reliability in the face of unexpected power surges or fluctuations. Added safety options include inputs for charger crash detection, flammable vapor monitoring, and flood detection along with inputs for remotely monitored E-Stop shutdown.

Nexphase - Icon - UPS.psd

UNINTERRUPTIBLE POWER SUPPLY

In the event of a power outage, an embedded UPS allows NexPhase™ to capture and deliver a snapshot of current system conditions. This feature empowers operators with detailed information, enabling swift and accurate remote diagnosis to expedite resolution and minimize downtime.

NexPhase - UNITE - PC - Breakers.jpg

UNITE™ WEB-BASED INTERFACE

An MQTTS Communication Protocol allows the NexPhase™ Hub to securely communicate with the web-based UNITE™ user interface. UNITE™ provides user-friendly access to monitoring information including:

Power Analysis

  • Current by Phase
  • Power Factor by Phase
  • Power Factor vs. Current
  • Voltage
  • Incoming utility power status
  • Max average power

Transaction Analysis

  • Energy consumption
  • Charge duration
  • EV Charger State
  • Max average power
  • Daily/weekly usage
  • Accumulated energy per post

NETWORK OVERSIGHT

Visualize your entire network geographically in a single map view. Confirm the status of all chargers and quickly key in on those that may require attention or maintenance.

DISCOVER UNITE™

ELECTRICAL

Utility Input 480 VAC Wye, 3-phase, L1, L2, L3 Neutral
Utility Connections Up to 5 parallel runs (L1, L2, L3, N)
1/2" diameter, 13/4" NEMA bolt spacing for compression lug
Current Transformer Ring type
Meter Socket 13 - 15 jaw ring type with test switch plate
Bus Capacity 2000 A
Main Service Circuit Breaker 480 VAC Wye connected, 3-phase, electronic adjustable trip unit: 1600 A frame (600 A - 1600 A)
Main Service Current Rating (SCCR) 65 kA
Ground Fault Detection Main service breaker
Surge Protection Device (SPD) Type 1/2, UL 1449
Arc Energy Reduction NEC 240.87 Compliant Maintenance Mode
Number of 480 V Branch Breakers Up to 4 electronic adjustable trip unit: 400 A frame (150 A - 400 A) OR 600 A frame (250 A - 600 A)
Output Connection L1, L2, L3: up to 2 parallel runs 2/0-600 kcmil (AL/CU, 75 deg C, mechanical lug)
Neutral: 1/2" diameter, 13/4" NEMA bolt spacing for compression lug
Ground: 6AWG-350 kcmil (AL/CU, 90 deg C, mechanical lug)
UPS Maintenance free uninterruptible capacitive power supply  (cULus Listed, UL 508)
Technician-Ready GFCI Outlet 1 (15 A Max)

PHYSICAL, ENVIRONMENT, COMPLIANCE, & SAFETY

Dimensions / Weight 391/2" Width  x 551/2 " Depth x 87" Height / 1,750 pounds (794 kg)
Enclosure NEMA 3R indoor/outdoor electrical cabinet
Electrical Code Designed for NFPA70; NEC2020
Certifications / Approvals UL Listed, UL891 (suitable for use as service equipment)
EUSERC Meets drawings 322, 325, 332, 345, 347, 354

MONITORING / CONTROL

Power Quality Monitoring - Current
- Voltage
- Power factor
- Apparent power
- Active power
- Reactive power
- Accumulated apparent energy
- Accumulated active energy
- Accumulated reactive energy
Transaction Data - Energy Consumption
- Charger power state
- Charger duration
- Max average power
- Daily/weekly usage
- Accumulated energy per post
Available Sensor Inputs Tilt (qty 4), water, hydrocarbon, emergency stop
Breaker Status Open / closed / trip
Remote Control Open / close each EV charger breaker via motor operators

SOFTWARE INTERFACE

Remote Connectivity Cellular or Ethernet Modem
Cloud Based Data Acquisition MQTTS Protocol
User Interface UNITE™ web-based, remote user interface (included - no subscription required)
API Data Integration Available upon request for integration with existing business software platforms

SWITCHGEAR SERIES COMPARISON

  NEXPHASE™ 2 SERIES 1,600 A NEXPHASE™ 3 SERIES 1,000 A NEXPHASE™ 3 SERIES 2,000 A
Main Bus 2,000 A 1,000 A 2,000 A
Main Breaker 1,600 A 1,000 A 2,000 A
Branch Breakers (Maximum) Up to 4 x 400 A or 2 x 600 A Up to 4 x 400 A Up to 4 x 600 A or 8 x 400 A
Charger Configurations Up to 4 x 200 kW or 2 x 360 kW Up to 4 x 180 kW Up to 4 x 360 kW or 8 x 180 kW
Transform Requirements 480 V Wye 480 V Wye 480 V Wye
CT Cabinet Integrated Integrated Integrated
Cabinet Mounted E-Stop No Optional Optional
Footprint 40" x 54" 48" x 54" 48" x 54"
NEMA Rating 3R 3R 3R
Safety Compliance UL 891 UL 891 UL 891
Meter Socket / Test Plate Yes No No
Utility Compliance EUSERC Alliant Energy, Xcel Energy, WE Energies, WPS Alliant Energy, Xcel Energy, WE Energies, WPS
Communication Ethernet / Cellular Ethernet / Cellular Ethernet / Cellular
Remote Power Cycle Yes Yes Yes
Remote Breaker Status Yes Yes Yes
Power Monitoring Yes (Main & Branches) Yes Yes
UNITE™ Software Included Included Included

NexPhase™ Smart EV Switchgear

Model Description
NP2-16-4X40-10X NexPhase™ Smart EV Switchgear, 2000 A bus, 1600 A main breaker, (4) 400 A branch breakers, with UNITE™ monitoring and control software
  • Note: X denotes specified utility identified during quoting process.